Softwall Clean Room No. 2900-50
(work table, hood and storage racks not included)
Softwall curtain (included on all models below) creates a
separate ante-chamber for gowning equipment staging.
Secifications
Dimensions:
6' x 8' or 6' x 10' (nominal inside; for exterior, add 4" to each dimension)
Height:
7' filter face to floor (hardwall designs); adjustable from 6 8' filter face to floor (softwall designs)
Materials:
Clean vinyl (softwall); acrylic or static-dissipative PVC (hardwall) panels
Powder-coated steel support frame and ceiling grid with mirror-finish 304 stainless steel trim strips
Complete turnkey clean room meets Class 100 (ISO 5) cleanliness standards for control of submicron particles, ensuring a clean compounding environment
Internal sliding curtain creates a separate gowning ante-room, in accord with USP-797 regulations
Includes three energy-saving, low-noise ceiling HEPA filter/fan units and one fluorescent illuminator
Powder-coated steel support frame creates a rigid, durable structure that requires no external bracing or ceiling support
Mirror-finish electropolished 304 stainless steel trim is easy to clean
Select softwall or hardwall design, in choice of three materials and two sizes
Telescoping frame uprights allow height adjustment of filter face between 6' and 8' above floor (overall height between 7' 2" and 9' 2") to accommodate low ceilings (Softwall designs only)
Modular design for fast installation, easy knock-down and storage
Terra's Compounding Clean Rooms provide the ideal environment for compounding sterile injectables and other critical operations.
Designed to meet the requirements of USP-797, they include three HEPA filter/fan units that provide a total of 1950 CFM of 99.99% particle-free air (measured at 0.3µm diameter), far exceeding the ISO 8 condition stipulated by USP-797 for compounding clean rooms. In fact, the primary processing area meets ISO 5 (Class 100) cleanliness standards.
Select between 6'W x 8'L and 6'W x 10'L floor plans. Both rooms include a sliding clean vinyl curtain that creates a separate antechamber for personnel gowning or product staging. In the typical configuration, the primary compounding room accommodates a 6'-long work bench, which provides ample space for a laminar flow hood, as stipulated by ISO-797 requirements (order bench and hood separately).
Softwall or Hardwall Designs Terra's softwall clean room features flexible cleanroom vinyl curtains that hang from a quick-install GripTrack along the outside perimeter. Curtains come in 4'-wide lengths and hang to about 3" above floor level. A 4'-wide strip shield entry is provided into the antechamber.
Hardwall designs are available with either rigid acrylic or static-dissipative PVC panels. Dissipative PVC offers superior resistance to chemicals, including alcohol and most germicides. By dissipating surface static charges that attract and hold particles, it also enhances contamination control. Two options are available for entry to a hardwall clean room: either parting strip shields or a rigid swing door (order below).
Includes (3) filter/fan units, (1) fluorescent light and internal roller-mount sliding curtain.
* See descriptions above.
** Order desired door style (strip shields or swing door) separately (see below).
(1) Acrylic is damaged by alcohol and other cleaning agents.
Parting Strip Shields
These 4"-W parting strips provide a convenient entry for hardwall clean rooms (included with softwall rooms listed above). Alternative frosted/clear design minimizes cling for easy parting. Price is per lineal foot; use quantity of (3) to create 3' door for standard hardwall rooms above.
Swing Doors
Aluminum frame with choice of acrylic or static-dissipative PVC panels and pneumatic closure. Standard mounting is on right side of 6' width, entering the antechamber area. Standard swing is outward (away from room). Dimensions: 80"H x 36"W.